Industrial Fire Extinguishing System

Applications:

1, Microwave room, meter wave room, electricity transformation and distribution room, UPS room in radio and television emission tower.

2, Switching room, control room, signal transfer room in the communication system; control room, electronic device room, computer room, relay room, electricity transformation and distribution room of the power plant; cross, dense and middle joint of the cable etc.

3, Various oftransformation and distribution cabinets, transformers, diesel generators, elevator control cabinets, cable troughs and tray

4, Special and important equipment with sealed shell

5, Various CNC machine tool equipment

6, Kitchen of the hotel and restaurant

Industrial Fire Extinguish System Brochure Download】 

※火探管主要参数


外径内径厚壁密度熔化点温度
Φ6.0 mmΦ4.0 mm1.0 mm ±0.1 mm1.05g/cm3 ±0.1g/cm3160℃ ± 10℃


※系统技术参数
装置类型装置释放
型式
公称工作
压力

最大工作
压力

工作温度
范围

单位容积所
需灭火剂的
最小量
火探管最
大长度
释放最大
长度
最大装置
系数
二氧化碳直接式5.17 Mpa15 Mpa(0~49)℃1.5kg/30m-0.6kg/L
火探灭火装置间接式12m
干粉直接式1.6 Mpa2.0 Mpa(-20~55)℃0.65kg/30m-0.85kg/L
火探灭火装置间接式12m


※常用选型表
装置类型型号灭火剂充装量 (kg)装置尺寸有效保护体积(m³)
二氧化碳
火探灭火装置
WZ-Q/T-TFDC33Φ140*5002.0
WZ-Q/T-TFDC66Φ140*10004.0
干粉
火探灭火装置
WZ-F/T-TFDF11Φ120*3502.0
WZ-F/T-TFDF33Φ133*5006.0
WZ-F/T-TFDF66Φ140*70012.0

  

  

Products

Product Name:

Product Introduction:


Industrial Fire Extinguishing System

Automatic Detecting and Fire Extinguishing Device (Temperature sensitive and self-starting fire extinguishing device) is a kind of newly developed fire extinguishing device in recent years at home and abroad, which is a simple, low cost, highly reliable, automatic and independent fire detecting/extinguishing system. This kind of extinguishing device adopts flexible fire detecting tube as the fire detecting and alarm components, and meanwhile this kind of fire detecting tube also can be the feeding and discharging tube of the extinguishant. The flexible fire detecting tube can be conveniently arranged near each potential fire point. Once the fire occurred, the detecting tube near the fire point shall be thermal cracking and discharge the extinguishant to put out the fire.